Central Battery Control Unit
รุ่น CCU 12-550 To CCU 12-1900 (Figure C)
Central Battery Control Unit by CCU Series or the central control unit is used to detect any abnormalities of the main power distribution system. In case of error or emergency, the unit is designed to allow the emergency lighting system to bear large loads or larger loads than that the automatic emergency light (complete unit) can. The 12 VDC unit is compatible with halogen lamp or MR16 LED lamp. The unit installation and usage are centrally controlled so that it supplies power to the lamp installed.
Technical Specifications
Mode of Operation | Non-Maintained |
Input Voltage | 220 VAC / 50Hz ± 10% |
Output Voltage | 12VDC |
Maximum Power Load | 550W / 620W / 720W / 850W / 1000W / 1100W / 1400W / 1900W (8 options) |
Battery Type | Sealed Lead-Acid Maintained Free |
Protections | • AC. Fuse. • DC. Circuit Breaker. • AC. Input Over & Under Voltage Protection. • Battery Low Voltage cut-off. |
Testing Systems | Manual Testing |
Charging Mode | Constant Voltage & Limit Current |
Charging Time | 10-15 Hrs. |
Backup Time | 2.0 Hrs. |
Housing | Electro-galvanized steel sheet 1mm. thick with epoxy powder coating. |
Dimensions (LxWxH) | 620 x 400 x 950 mm. |
Weight | 171.00 Kg. |
IP Rating | 20 |
Features
- Allowing testing with a switch on the front panel.
- Automatically recharged with constant voltage and limited current.
- Battery overcharge protection circuit prevents overcharge which is the cause of battery swelling.
- Battery discharge protection circuit prolongs the battery life.
- Under voltage protection circuit allows the unit to automatically activate the emergency light in case any fault occurs in the the main power distribution system or in case of power failure (140-160 VAC).
- Over voltage protection circuit allows the unit to automatically activate the emergency light in case any fault occurs in the the main power distribution system or in case of power failure (260-270 VAC).
Indicators
AC. VOLTMETER | Indicating the input voltage. |
DC. VOLTMETER | Indicating the battery voltage. |
LED H1 | Indicating the status of the input under voltage or over voltage. |
LED Charge/Full | Indicating charging status. |
SWITCH TEST | For testing the device’s availability (during normal circumstance) |
AC. FUSE | Short-circuit protection of AC input. |
LED MAIN | Indicating the status of the input voltage of 220VAC. |
LED DC.POWER | Indicating the status of the output voltage. |
LED FAIL | Indicating the failure status of the control unit. |
CCU 12V Series (Figure C) | Spec Sheets
Model | Power (Wattage) | Battery Capacity | Back up (hr.) | Length (mm) | Width (mm) | Height (mm) | Weight (kgs.) |
---|---|---|---|---|---|---|---|
CCU 12-550 | 550 | 12V 130Ah | 2.0 | 620 | 350 | 750 | 74.00 |
CCU 12-620 | 620 | 12V 130Ah | 2.0 | 620 | 350 | 750 | 76.00 |
CCU 12-720 | 720 | 12V 150Ah | 2.0 | 620 | 350 | 750 | 77.00 |
CCU 12-850 | 850 | 12V 200Ah | 2.0 | 620 | 350 | 750 | 99.50 |
CCU 12-1000 | 1000 | 12V 200Ah | 2.0 | 620 | 350 | 750 | 99.50 |
CCU 12-1100 | 1100 | 12V 130Ah x 2 | 2.0 | 620 | 400 | 950 | 119.00 |
CCU 12-1400 | 1400 | 12V 150Ah x 2 | 2.0 | 620 | 400 | 950 | 125.00 |
CCU 12-1900 | 1900 | 12V 220Ah x 2 | 2.0 | 620 | 400 | 950 | 171.00 |